CI845

System 800xA offers flexible and modular I/O solutions through fieldbus technologies, wireless I/O and hardwired I/O systems like S800 and S900. The system is now enhanced with S800 on Ethernet and Select I/O. Select I/O allows to connect each signal coming from the field individually. Select I/O is Ethernet connected and consist of single channel granular Signal Conditioning Modules (SCM).

CI845 is a Ethernet Fieldbus Communication Interface Module for connection of S800 I/O or Select I/O to Ethernet. For redundant configuration two Fieldbus Communication Interfaces CI845, two Ethernet Adapters TC810 and one TU860 or one TU865 are needed. For Select I/O High Integrity SIL3 one HI880 is needed.

System 800xA offers flexible and modular I/O solutions through fieldbus technologies, wireless I/O and hardwired I/O systems like S800 and S900. The system is now enhanced with Select I/O that allows to condition each signal coming from the field individually. Select I/O is Ethernet connected and consist of single channel granular Signal Conditioning Modules (SCM).

Features and benefits

  • Can be used as single or redundant
  • Supports both Select I/O and S800 on Ethernet
    • Supports 12 single or 12 redundant S800 I/O modules
    • Supports up to 192 Select I/O channels
  • Possible to use with single ar redundant 24V power supplies
  • Built-in power voting
  • Built-in supervision of power supply A and power supply B
  • Built-in cabinet temperature measurement
  • Built-in diagnostics
  • Soft marshalling
  • Optimized engineering
  • HART v7, HART pass-through and HART variables to the application
  • Sequense of Events
  • Supports hot swap
  • Can be used in hazardous area
  • Mechanical locking slider which turns off power before removal
  • Mechanical keying